To drain a Well-X-Trol, switch off power to the pump and open a faucet until the tank is empty and pressure is gone. Then check the precharge at the air valve and set it 2 psi below the pressure switch cut-in. Amtrol warns not to add air to a tank in service that has lost air or shows corrosion, because that can signal internal damage and a rupture risk.
How a Well-X-Trol works
A Well-X-Trol holds a pocket of compressed air above a diaphragm. As the pump fills the tank with water, the air squeezes and pressure rises until the switch turns the pump off. When you open a tap, the air pushes water out and pressure falls until the switch starts the pump again. The water delivered between those points is the drawdown.
Amtrol's manual sums up why size matters: the larger the tank, the greater the drawdown and the less the pump needs to run, which extends pump life and steadies pressure. The tank also cushions pressure spikes and gives the pump a minimum run time.
Well-X-Trol sizes and drawdown
Model numbers do not show volume directly, so use Amtrol's spec card. Drawdown is the useful figure, and it shrinks as system pressure rises. The card also lists a maximum working pressure of 150 psig for all models and a factory precharge of 38 psig, which suits a 40/60 switch but is too high for the common 30/50 setting. That is why a new tank must be checked and adjusted before it goes into service, not simply plumbed in as it arrives. Amtrol also makes horizontal, in-line and underground versions with different connections, so match the model to the space as well as the volume.
| Model | Tank volume | Drawdown at 30/50 psi | Drawdown at 40/60 psi | Connection |
|---|---|---|---|---|
| WX-201 | 14.0 gal | 4.3 gal | 3.8 gal | 1 in NPTF |
| WX-202 | 20.0 gal | 6.2 gal | 5.4 gal | 1 in NPTF |
| WX-203 | 32.0 gal | 9.9 gal | 8.6 gal | 1 in NPTF |
| WX-250 | 44.0 gal | 13.6 gal | 11.8 gal | 1-1/4 in NPTF |
| WX-251 | 62.0 gal | 19.2 gal | 16.6 gal | 1-1/4 in NPTF |
| WX-350 | 119.0 gal | 36.8 gal | 31.9 gal | 1-1/4 in NPTF |
Choosing the right size
Amtrol's quick sizing table matches tank to pump flow and minimum run time. For pumps up to 3/4 hp it aims for one minute of run time; above 3/4 hp, two minutes. At 30/50 psi, a pump delivering about 5 GPM is matched to the WX-202, and about 10 GPM to the WX-203, for the smaller pump class. Bigger pumps and higher pressure settings push you to the larger models or to two tanks.
When in doubt, go larger. The manual's point is simple: fewer pump starts mean longer pump and tank life. The pressure tank sizing guide walks through the calculation.
How to drain the tank and check precharge
Amtrol says precharge adjustments should be made only with the tank empty of water and the system off, and at ambient temperature. The steps below follow its start-up and adjustment procedure. Use an accurate tire gauge on the air valve at the top of the tank. Reading the precharge with water still inside gives a false, higher figure, because the water pressure pushes back on the diaphragm. The tank must be fully empty for the reading to mean anything, which is why draining comes first.
- Turn off power to the pump at the breaker.
- Open a faucet or the tank drain and let the tank empty fully.
- Remove the air valve cap and read the precharge with a gauge.
- Set it 2 psi below the switch cut-in, for example 38 psi for 40/60.
- Replace the cap, close the faucet and restore power.
- Run the system and watch one full pump cycle.
Amtrol's warning about adding air
This is the part of the manual most owners never read. Amtrol warns not to adjust or add pressure if the tank has lost air, if there is visible exterior corrosion, or if pump cycle time or precharge has dropped compared with the original setting. Its reason is that air loss can mean internal corrosion, and re-pressurizing a weakened tank could cause it to rupture or explode.
Amtrol also calls for a relief valve set to open at excessive pressure, around 125 psig or more, at the tank's connection to the system, sized to the pump's capacity. It wants the tank mounted vertically, kept from freezing and from water hotter than 130 °F, and inspected yearly by a professional, more often as it ages.
Signs your Well-X-Trol is failing
The classic sign is rapid cycling: the pump starts and stops every few seconds as you run water. Red Lion's troubleshooting guide lists a waterlogged tank, incorrect precharge and air leaks above the water level among the causes. Water spitting from the air valve when you press it means the diaphragm has failed and water has reached the air side. Rust, damp spots or weeping at the connection are reasons to replace rather than recharge, given Amtrol's warning.
A failing switch can look like a tank problem, so read the pressure gauge through a cycle. If pressure swings between the switch settings correctly but the pump runs only briefly, suspect the tank. Amtrol's warranty on WX models is seven years. For replacement choices, see the well pump hub, which also lists the WaterWorker tanks.
Common mistakes
- Checking precharge with water still in the tank.
- Re-pressurizing an older tank that has lost air without a professional's inspection.
- Setting precharge to the factory figure instead of 2 psi below cut-in.
- Installing without the relief valve Amtrol calls for.
- Mounting the tank where a leak would damage finished space below.
Products that fit

Amtrol WX-202 Well-X-Trol Pressure Tank
20 gallon Well-X-Trol with about 6.2 gal of drawdown at 30/50 psi.

Amtrol WX-203 Well-X-Trol Well Tank
32 gallon model with about 9.9 gal of drawdown at 30/50 psi.

WaterWorker HT-32B Pressure Tank
Tank from Amtrol's WaterWorker line, an alternative pre-charged well tank family offered in several smaller sizes.

Square D FSG2J21CP 30/50 PSI Pressure Switch
30/50 psi pressure switch that sets the cut-in the precharge must match.
Questions readers ask
How do I drain a Well-X-Trol pressure tank?
Turn off power to the pump, then open a faucet or the tank drain until water stops and pressure is gone. Amtrol says precharge should be checked and adjusted only with the tank empty and the system off.
What should the precharge be on a Well-X-Trol?
Amtrol says 2 psi below the pressure switch cut-in, for example 38 psi on a 40/60 switch or 28 psi on 30/50. Its tanks ship at 38 psig, so adjust if your switch is set lower.
How big is a WX-202 and a WX-203?
Amtrol's spec card lists the WX-202 at 20.0 gallons and the WX-203 at 32.0 gallons, with drawdowns of about 6.2 and 9.9 gallons at 30/50 psi. Both stand vertically and share a 1 in NPTF connection.